505 NEMA Enclosed Reversing Starter

505-DAA


Representative Rendering, Not The Actual Product

505 NEMA Enclosed Reversing Starter ,SIZE 3, Type 1 General Purpose Surface Mounting, 230-240V 60Hz, with Eutectic Alloy Overload Relay, , ,

Product Details

ASSEMBLY
Assembly?Factory Assembled
SYSTEM VOLTAGE DATA
Supply Voltage240V 60Hz
PhasesThree Phase
STARTER DATA
Horsepower30 HP
NEMA SizeNEMA 3
Enclosure TypeNEMA Type 1 General Purpose Enclosure, Surface Mounting
OPTIONS
Overload Relay TypeEutectic Alloy
Full Load AmpsEutectic Overload
IMPORTANT INFORMATION
Enclosure Size [length x width x depth]30 x 20 x 9 in.

Specifications

Electrical Ratings

Load Voltage115…575 (V)
Continuous Current Rating90 (A)
Service Limit Current Rating104 (A)
Maximum Hp Rating (Non-plugging and non-jogging duty) Single-Phase- (Hp)
Maximum Hp Rating (Non-plugging and non-jogging duty) Three-Phase50 (Hp)
Maximum Circuit Closing Inrush Current, Peak Including Offset947 (A)

Mechanical Ratings

Mechanical Life5 (Millions of Operations)
Maximum Number of Auxiliary Contacts8
Pick-up Operating Time (Average)37 (ms)
Drop-out Operating Time (Average)20 (ms)

Construction

Wire size for Power Terminals8…1/0 (AWG)
Required Torque150 (lb•in)
Type of Power TerminalPressure Terminals

Environment Ratings

Operating PositionVertical
Temperature Range-13…+149°F(-25…+65°C)
Altitude10,000 (feet before derating)
Corrosion-ResistanceAll metal parts are treated for corrosion-resistance

Replacement Parts

Product TypeSpare Part
Catalog NumberCD-254
DescriptionCoil,230/240V 60HZ For Starter Or Contactor
Quantity2
Product TypeContactor
Catalog Number500F-DOD930
Description500F, 500FC NEMA AC/DC Contactor,Motor Loads,Feed-Through ,SIZE 3, Open, 115-120V 60Hz, 3 Power Poles, Yes , 90 , 110/120V 50/60 Hz ,
Quantity1
Additional InformationNEMA Contactor and Starter Specification
Product TypeOverload
Catalog Number592-EUTD
DescriptionNEMA Eutectic Alloy Overload Relay, Manual Reset, 125A, N.C. Contact
Quantity1

Supporting Documentation and Downloads