509 NEMA Enclosed Non-Combination Starter

509-FAA

NEMA Full Voltage Non-Reversing Starter,SIZE 5,230-240V 60Hz,Type 1 General Purpose , with Eutectic Alloy Overload Relay

Product Details

ASSEMBLY
Hazardous LocationNo
STARTER DATA
Supply Voltage240V 60Hz
Phases3 Phase
Horsepower100 HP
NEMA SizeNEMA 5
Enclosure CodeType 1 General Purpose
Control Voltage220/240V 50/60Hz
OPTIONS
Overload Relay TypeEutectic Alloy
Full Load AmpsEutectic Overload - Select a heater element based on trip class and Motor FLA
IMPORTANT INFORMATION
Enclosure Size [length x width x depth]50 x 22 x 11 in.

Specifications

Electrical Ratings

Load Voltage115…575 (V)
Continuous Current Rating270 (A)
Service Limit Current Rating311 (A)
Maximum Hp Rating (Non-plugging and non-jogging duty) Single-Phase- (Hp)
Maximum Hp Rating (Non-plugging and non-jogging duty) Three-Phase100 (Hp)
Maximum Circuit Closing Inrush Current, Peak Including Offset3163 (A)

Mechanical Ratings

Mechanical Life5 (Millions of Operations)
Maximum Number of Auxiliary Contacts8
Pick-up Operating Time (Average)25 (ms)
Drop-out Operating Time (Average)18 (ms)

Construction

Wire size for Power Terminals4 AWG…500 MCM (AWG)
Required Torque375 (lb•in)
Type of Power TerminalPressure Terminals

Environment Ratings

Operating PositionVertical
Temperature Range-13…+149°F(-25…+65°C)
Altitude10,000 (feet before derating)
Corrosion-ResistanceAll metal parts are treated for corrosion-resistance

Replacement Parts

Product TypeSpare Part
Catalog NumberAF-254
DescriptionCoil,240V/60HZ 220V/50HZ For Starter Or Contactor
Quantity1
Product TypeContactor
Catalog Number500F-FOD930
Description500F, 500FC NEMA AC/DC Contactor,Motor Loads,Feed-Through ,SIZE 5, Open, 115-120V 60Hz, 3 Power Poles, Yes , 270 , 110/120V 50/60 Hz ,
Quantity1
Additional InformationNEMA Contactor and Starter Specification