509 NEMA Enclosed Non-Combination Starter

509-FJH-XXX

NEMA Full Voltage Non-Reversing Starter,SIZE 5,200-208V 60Hz,Type 3R/4/12, Rainproof, Dusttight Industrial Use Enclosure, Provision for Mounting an Overload Relay (field installation)

Product Details

ASSEMBLY
Hazardous LocationNo
STARTER DATA
Supply Voltage208V 60Hz
Phases3 Phase
Horsepower75 HP
NEMA SizeNEMA 5
Enclosure CodeType 3R/4/12 Rainproof, Dusttight Industrial Use
Control Voltage208V 60Hz
OPTIONS
Overload Relay TypeProvision for Mounting an Overload Relay (field installation)
Full Load AmpsProvision for Mounting an Overload Relay (field installation)
IMPORTANT INFORMATION
Enclosure Size [length x width x depth]50 x 22 x 11 in.
Overload Relay SelectionThese products are intended for field installation of Bulletin 592 eutectic or solid state overload relays. They ship in a starter carton with provisions for mounting the overload relay (includes a starter mounting plate, screws/bolts and instructions)

Specifications

Electrical Ratings

Load Voltage115…575 (V)
Continuous Current Rating270 (A)
Service Limit Current Rating311 (A)
Maximum Hp Rating (Non-plugging and non-jogging duty) Single-Phase- (Hp)
Maximum Hp Rating (Non-plugging and non-jogging duty) Three-Phase75 (Hp)
Maximum Circuit Closing Inrush Current, Peak Including Offset3163 (A)

Mechanical Ratings

Mechanical Life5 (Millions of Operations)
Maximum Number of Auxiliary Contacts8
Pick-up Operating Time (Average)25 (ms)
Drop-out Operating Time (Average)18 (ms)

Construction

Wire size for Power Terminals4 AWG…500 MCM (AWG)
Required Torque375 (lb•in)
Type of Power TerminalPressure Terminals

Environment Ratings

Operating PositionVertical
Temperature Range-13…+131°F(-25…+55°C)
Altitude10,000 (feet before derating)
Corrosion-ResistanceAll metal parts are treated for corrosion-resistance

Replacement Parts

Product TypeSpare Part
Catalog NumberAF-249
DescriptionCoil,200-208V 60HZ For Starter Or Contactor
Quantity1
Product TypeContactor
Catalog Number500F-FOD930
Description500F, 500FC NEMA AC/DC Contactor,Motor Loads,Feed-Through ,SIZE 5, Open, 115-120V 60Hz, 3 Power Poles, Yes , 270 , 110/120V 50/60 Hz ,
Quantity1
Additional InformationNEMA Contactor and Starter Specification

Supporting Documentation and Downloads