509 NEMA Enclosed Non-Combination Starter

509-TAC-3

NEMA Full Voltage Non-Reversing Starter,SIZE 00,575-600V 60Hz,Type 1 General Purpose , with Eutectic Alloy Overload Relay

Product Details

ASSEMBLY
Hazardous LocationNo
STARTER DATA
Phases3 Phase
NEMA SizeNEMA 00
Enclosure CodeType 1 General Purpose
Control Voltage550/600V 50/60 Hz
OPTIONS
Overload Relay TypeEutectic Alloy
Full Load AmpsEutectic Overload - Select a heater element based on trip class and Motor FLA
Factory Installed ModificationsHAND-OFF-AUTO Selector Switch
IMPORTANT INFORMATION
Enclosure Size [length x width x depth]10 x 7 x 5 in.

Specifications

Electrical Ratings

Load Voltage115…575 (V)
Continuous Current Rating9 (A)
Service Limit Current Rating11 (A)
Maximum Hp Rating (Non-plugging and non-jogging duty) Single-Phase- (Hp)
Maximum Hp Rating (Non-plugging and non-jogging duty) Three-Phase2 (Hp)
Maximum Circuit Closing Inrush Current, Peak Including Offset87 (A)

Mechanical Ratings

Mechanical Life10 (Millions of Operations)
Maximum Number of Auxiliary Contacts5
Pick-up Operating Time (Average)20 (ms)
Drop-out Operating Time (Average)16 (ms)

Construction

Wire size for Power Terminals16…10 (AWG)
Required Torque9 (lb•in)
Type of Power TerminalPressure Terminals

Environment Ratings

Operating PositionHorizontal
Temperature Range-13…+149°F(-25…+65°C)
Altitude10,000 (feet before derating)
Corrosion-ResistanceAll metal parts are treated for corrosion-resistance

Replacement Parts

Product TypeSpare Part
Catalog NumberTA-476
DescriptionCoil,550V 50HZ,600V 60HZ FOR Contactor
Quantity1

Supporting Documentation and Downloads