509 NEMA Enclosed Non-Combination Starter

509-TAD-A2E

NEMA Full Voltage Non-Reversing Starter,SIZE 00,115-120V 60Hz,Type 1 General Purpose

Product Details

ASSEMBLY
Hazardous LocationNo
STARTER DATA
Phases3 Phase
NEMA SizeNEMA 00
Enclosure CodeType 1 General Purpose
Control Voltage110/120V 50/60 Hz
OPTIONS
Overload Relay TypeE100 Solid State Overload Relay
Full Load Amps1.0...5.0
IMPORTANT INFORMATION
Enclosure Size [length x width x depth]10 x 7 x 5 in.

Specifications

Electrical Ratings

Load Voltage115…575 (V)
Continuous Current Rating9 (A)
Service Limit Current Rating11 (A)
Maximum Hp Rating (Non-plugging and non-jogging duty) Single-Phase- (Hp)
Maximum Hp Rating (Non-plugging and non-jogging duty) Three-Phase1-1/2 (Hp)
Maximum Circuit Closing Inrush Current, Peak Including Offset87 (A)

Mechanical Ratings

Mechanical Life10 (Millions of Operations)
Maximum Number of Auxiliary Contacts5
Pick-up Operating Time (Average)20 (ms)
Drop-out Operating Time (Average)16 (ms)

Construction

Wire size for Power Terminals16…10 (AWG)
Required Torque9 (lb•in)
Type of Power TerminalPressure Terminals

Environment Ratings

Operating PositionHorizontal
Temperature Range-13…+131°F(-25…+55°C)
Altitude10,000 (feet before derating)
Corrosion-ResistanceAll metal parts are treated for corrosion-resistance

Replacement Parts

Product TypeSpare Part
Catalog NumberTA-473
DescriptionCoil,110V 50HZ For Contactor
Quantity1